- On request
FUENTES DE PODER
Última actualización
CP-BBU 115-230VAC / 24VDC
Weidmuller
Delivery time :
(Our products have limited warranty, please check our terms)
(Delivery 1-2 days for products in stock)
Connection range
AWG26-12 (0.1-4.0 mm²)
Input current
1 A @ 115 V AC; 0.6 A @ 230 V AC
Input frequency
50/ 60 Hz
Input fuse
2 A time-lag fuse (internal)
Input voltage (voltage mode input)
85...265 V AC; 120...300 V DC. typ. 115...230 V AC ±10%
Inrush Current Limitation
Thermistor
Surge protection
Varistor
Wire connection method
Screw connection
Battery charging current
2 A
Battery voltage
27.3 V
Connection range
AWG26-12 (0.1-4.0 mm²)
Control at input voltage
0.2%
Mains failure bridge-over time for 115 V AC
24 ms
Mains failure bridge-over time for 230 V AC
190 ms
Max. residual ripple
< 50 mVeff
Output current
max. 15 A / max. 9.0 A for the power supply unit
Output power
360 W
Output voltage type
DC
Wire connection method
Screw connection
Version
UPS control unit, 24 V
Order No.
9916280024
Type
CP-BBU 115-230VAC / 24VDC
GTIN (EAN)
4032248217878
Qty.
1 items
Delivery status
This article will no longer be available in the future.
Available until
31.12.2014
Alternative product
1370050010
Depth
161 mm
Depth (inches)
6.339 inch
Height
127.5 mm
Height (inches)
5.02 inch
Width
72.5 mm
Width (inches)
2.854 inch
Net weight
1,150 g
The UPS control unit together with the associated battery module and the power supply unit form a complete DC UPS system. In normal operation, the input voltage from the UPS control unit is connected directly to the load. In the event of a mains failure (drop of the DC input voltage) the system switches instantly to bat tery operation.
Once the mains supply has been restored, the system switches back to normal operation and the battery is fully recharged by the integrated charger.
Three relay outputs, as well as three additional active transistor outputs and a control input to lock battery operation, provide full remote control by means of SPS or DCS control. Numerous modes of operation and an easy-to-use status display provide rapid fault diagnosis and optimum
customisation to the application.